3/3 10K~30K Online UPS Uninterruptible Power Supply System Version: 1.0 User Manual
7 use AWG 8 or thicker wire for Phase and AWG 4 or thicker wire for Neutral for safety and efficiency. NOTE 5: The selections for color of wir
8 not, please install it carefully. Switch off the battery breaker before installation. NOTE: Set the battery pack breaker in “OFF” position and then
9 Wiring diagram of parallel system for 30K(L) 2-5. Software Installation For optimal computer system protection, install UPS monitoring software t
10 3. Operations 3-1. Button Operation Button Function ON/Enter Button Turn on the UPS: Press and hold the button more than 0.5s to turn on t
11 LCD Panel: Display Function Backup time information Indicates the battery discharge time in numbers H: hours, M: minutes, S: seconds Fau
12 Battery information Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates the battery is not connected. Indicates lo
13 3. Connect devices to UPS After the UPS is turned on, you can connect devices to the UPS. 1) Turn on the UPS first and then switch on the devic
14 2) In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the line input breaker(for dual input
15 3-5. Parallel Operation 1. Parallel system initial startup First of all, please make sure all of the UPSs are parallel models and have the same co
16 Second method: 1) If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the load and shut down the system
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the f
17 AB The first line BC The second line CA The third line 3-7. LCD Setting There are three parameters to set up the UPS. Refer to following diagr
18 20 Output C voltage calibration Y Y Y *Y means that this program can be set in this mode. Note: All parameter settings will be saved only when
19 04: Frequency range for bypass Interface Setting Parameter 2: Set the acceptable low frequency for bypass. 50 Hz system: Setting range is fr
20 09: Maximum battery discharge time setting Interface Setting Parameter 3: 000~999: Set the maximum discharge time from 0 min to 999 min. UPS
21 13: Battery voltage calibration Interface Setting Parameter 2: Select “Add” or “Sub” function to adjust battery voltage to real figure. Pa
22 18: Output A voltage calibration Interface Setting Parameter 2: it always shows OP.V as output voltage. Parameter 3: it shows the interna
23 Operating mode/status UPS Power On Description When UPS is powered on, it will enter into this mode for a few seconds as initializing the CPU a
24 ECO mode Description When the input voltage is within voltage regulation range and ECO mode is enabled, UPS will bypass voltage to output fo
25 CVCF mode Description When the output frequency is set to “CF”, the inverter will output constant frequency (50 Hz or 60 Hz). At this mod
26 Bypass mode Description When input voltage is within acceptable range and bypass is enabled, turn off the UPS and it will enter Bypass mode. Ala
Table of Contents 1. SAFETY AND EMC INSTRUCTIONS ... 1
27 Warning status Description If some errors occur in the UPS (but it is still running normally), it will show one more screen to represent the w
28 3-9. Fault Code Fault code Fault event Icon Fault code Fault event Icon 01 Bus start failure None 1A Inverter A negative power fault None 02 Bus o
29 3-11.Warning Code Warning code Warning event Warning code Warning event 01 Battery unconnected 10 L1 IP fuse broken* 02 IP Neutral loss 11 L2 IP f
30 4. Trouble Shooting If the UPS system does not operate correctly, please solve the problem by using the table below. Symptom Possible cause Rem
31 Symptom Possible cause Remedy The warning code 02 is shown, the icon flashes on LCD display, and alarm beeps every second. The input
32 5. Storage and Maintenance 5-1. Storage Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry lo
33 6. Specifications MODEL 10K 10KL 15K 15KL 20K 20KL 30K 30KL CAPACITY* 10000VA / 9000W 15000VA / 13500W 20000VA / 18000W 30000VA / 27000W INPUT Vo
1 1. Safety and EMC instructions Please read carefully the following user manual and the safety instructions before installing the unit or using th
2 1-4. Connection Warnings There is no standard backfeed protection inside, please isolate the UPS before working according to this circuit. The
3 1-5. Operation Do not disconnect the earth conductor cable on the UPS or the building wiring terminals in any time since this would cancel the pr
4 2. Installation and Operation There are two different types of online UPS: standard and long-run models. Please refer to the following model table
5 2-2. Rear Panel View Diagram 1: 10K(L)/15K(L)/20K(L) Diagram 2: 30KL Rear Panel Diagram 3: 30K Rear Panel
6 5. Parallel port (only available for parallel model) 6. Intelligent slot 7. Power stage fan 8. External battery connector (Only available for l